Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - UNDERGROUND
Permit Number - T02CM05779
Inspection Description - ELECTRIC - UNDERGROUND
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/20/2003 | ELECTRIC - UNDERGROUND | Approved | IVRS - Inspection 0000* | |
| 04/11/2003 | ELECTRIC - UNDERGROUND | Not ready for Inspection | IVRS - Inspection 0000*1.) IDENTIFY GROUNDED CONDUCTORS. 2.) TIGHTEN GROUND LUGS TO POLE. |
|
| 04/10/2003 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection 0000* | |
| 04/08/2003 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection 0000*MAINTAIN DEPTHS AS PER CODE 300-5 OK AS MARKED. | |
| 04/04/2003 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection 0000*OK 3 POLE BASES AND GROUNDING AS MARKED. | |
| 04/01/2003 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection 0000*OK 16 POLE BASE GROUNDING AS MARKED. | |
| 03/31/2003 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection 0000*OK 4 POLES BASE FOR GROUNDING AS MARKED. OK 8 POLE BASE AS MARKED OK PVC CONDUITS AS MARKED. |
|
| 03/26/2003 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection 0000*OK 4 POLE BASE AND 1 1/4" & 3/4" PVC AS MARKED. | |
| 03/24/2003 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection 0000*OK 3 POLE BASES AS MARKED. | |
| 03/20/2003 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection 0000*OK 5 POLE BASES AND 3/4" PVC AS MARKED. | |
| 03/19/2003 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection 0000*OK 4-3" PVC CONDUITS TRANFORMER OUT 70' OK 5 POLE BASES AND 3/4" PVC AS MARKED. | |
| 03/17/2003 | ELECTRIC - UNDERGROUND | Not ready for Inspection | IVRS - Inspection 0000* | |
| 03/14/2003 | ELECTRIC - UNDERGROUND | Not ready for Inspection | IVRS - Inspection 0000* | |
| 03/13/2003 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection 0000* 1.) DB-120 15 NOT LISTED FOR ELECTRICAL USAGE OK POLE BASE (9) AND 3/4" PVC AS MARKED. |
|
| 03/11/2003 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection 0000*OK AREAS AS MARKED. 1.) SPLIT BOLTS NOT ALLOWED MORE THAN A RUN & A TAP ALSO. SPLICES TO BE INSULATED EQUAL TO ORGINIAL CONDUCTORS. |
|
| 03/07/2003 | ELECTRIC - UNDERGROUND | Not ready for Inspection | IVRS - Inspection 0000* | |
| 03/06/2003 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection 0000*OK PVC CONDUIT AS MARKED. | |
| 03/05/2003 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection 0000*OK 3/4" & 1" PVC AS MARKED. | |
| 03/04/2003 | ELECTRIC - UNDERGROUND | Not ready for Inspection | IVRS - Inspection 0000* | |
| 03/03/2003 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection 0000*OK 3/4" & 1" PVC FOR POLES AS MARKED ON PLANS. |