Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/04/2003 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection 0000*HAVE LETTER ON INSULATION. | |
| 02/03/2003 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000* | |
| 02/03/2003 | PLUMBING - INTERMEDIATE | Partial Approval | TEST OK TO COVER S.T.O.I. | |
| 01/29/2003 | PLUMBING - INTERMEDIATE | Not ready for Inspection | 1.) SEE PLANS FOR CO. 2.) PROVIDE WATER TEST TO ROOF AS REQUIRED BY CODE ON WASTE VENT. 3.) CODE VIOLATION ON VENT FOR SINK 6" ABOVE FLOOD RIM OF FIXTURE. 4.) PROVIDE CLEVIS HANGERS ON VENTS THROU ROOF & MID STORY ANCHORS. 5.) PLEASE INSTALL RELIEF LINE. 6.) PLEASE NOTE PEDICURE STATIONS MAY REQUIRE BACK FLOW DEVICES. |