Permit: T02CM05762

Parcel: 11004345C


Addresses:

3305 N SWAN RD #103

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
02/27/2003 ELECTRIC - FINAL Approved IVRS - Inspection 0000*OK FINAL SUBJECT TO ALL INSPECTIONS
02/26/2003 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*
1.) GROUNDED CONDUCTOR TO BE MARKED AS PER 200-6
2.) SUPPORT CONDUIT ABOVE CEILING AS PER CODES 300-11 & 348-13 INDEPENENT WIRES ATTACHED AT BOTH ENDS AND 3' T0 10'.
3.) AN APPROVED EXTENDER RING IS NEEDED WHERE MORE THAN 1/4" FROM BOX TO DEVICE 370-20.
02/25/2003 ELECTRIC - FINAL Denied IVRS - Inspection 0935*WORK PROGRESS IN NOT HAPPENING. A REFEE HAS BEEN ASSESSED.
02/24/2003 ELECTRIC - FINAL Denied IVRS - Inspection 0999*
1.) TIGHEN LOOSE FITTINGS AT WATER HEATER
2.) USE AN APPROVED LISTED COVER PLATE.
3.) WHEN USING TAPE TO IDENTIFY CONDUCTORS IT IS TO ENCIRCE CONDUCTORS.
4.) A EXTENDER RING IS NEEDED WHERE 1/4" OR MORE FROM BOX TO DEVICE.
5.) CONDUCTOR TO BE INSTALLED IN A CLOCK WISE DIRECTION UNDER SCREWS
6.) TIGHTEN GROUND SCREWS TO CONDUCTOR.
7.) ALL METER BOXES TO BE GROUNDED
8.) FINISH ITEM #1,4, & 6 OF INSPECTION DATED 2-10-3.
02/10/2003 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*