Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T02CM05762
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/27/2003 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000*OK FINAL SUBJECT TO ALL INSPECTIONS | |
02/26/2003 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000* 1.) GROUNDED CONDUCTOR TO BE MARKED AS PER 200-6 2.) SUPPORT CONDUIT ABOVE CEILING AS PER CODES 300-11 & 348-13 INDEPENENT WIRES ATTACHED AT BOTH ENDS AND 3' T0 10'. 3.) AN APPROVED EXTENDER RING IS NEEDED WHERE MORE THAN 1/4" FROM BOX TO DEVICE 370-20. |
|
02/25/2003 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0935*WORK PROGRESS IN NOT HAPPENING. A REFEE HAS BEEN ASSESSED. | |
02/24/2003 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999* 1.) TIGHEN LOOSE FITTINGS AT WATER HEATER 2.) USE AN APPROVED LISTED COVER PLATE. 3.) WHEN USING TAPE TO IDENTIFY CONDUCTORS IT IS TO ENCIRCE CONDUCTORS. 4.) A EXTENDER RING IS NEEDED WHERE 1/4" OR MORE FROM BOX TO DEVICE. 5.) CONDUCTOR TO BE INSTALLED IN A CLOCK WISE DIRECTION UNDER SCREWS 6.) TIGHTEN GROUND SCREWS TO CONDUCTOR. 7.) ALL METER BOXES TO BE GROUNDED 8.) FINISH ITEM #1,4, & 6 OF INSPECTION DATED 2-10-3. |
|
02/10/2003 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000* |