Permit: T02CM05762

Parcel: 11004345C


Addresses:

3305 N SWAN RD #103


Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T02CM05762

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
02/27/2003 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection 0000*
02/26/2003 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection 0000*
02/25/2003 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection 0935*
02/10/2003 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection 0999*
01/29/2003 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection 0000*OK TEMP POWER FOR TEST SUBJECT TO BOND AND OTHER INSPECTORS.
1.) GROUNDED CONDUCTOR TO BE THE COLOR OR MARKED AS PER 200-6.
2.) FILL UNUSED OPENING IN PANEL
3.) FINISH INSTALLING COVER PLATES.
4.) SUPPORT VDV CABLES UP OFF OF GRID AND PER CODE 300-11.
5.) WHEN USING MANUFACTURES HOLD DOWN CLIPS THEY MUST BE EFFECTIVE ALSO BOTH END TO BE SECURED TO GRID.
6.) SUPPORT CONDUIT AS PER CODE 300-11 AND 348-13.
01/21/2003 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection 0999*1.) SUPPORT CONDUITS AS PER CODE 3' FROM BOXES & FITTINGS AND AS PER 300-11 ABOVE CEILING.
2.) WE HAVE BROKEN M/C CABLE ARMOR AT FITTING.
3.) PLEASE CK CONDUCTOR FILL IN 4 SQ 130K.
4.) RECESSED CANS TO HAVE A SUPPORT WIRE.
5.) SUPPORT M/C CABLE CONDUIT ABOVE CEILING ON INDEPENTANT WIRES AS PER CODE 300-11.
6.) M/C CABLE TO HAVE CORRECT SIZED 1 HOLE STRAP FOR SUPPORT.
7.) UNDERGROUND INSTALLED WITH OUT INSPECTION.
8.) PLEASE ADD INTERMEIDATE ELECTRIC TO PERMIT CLOSE.