Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T02CM05746

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
07/03/2003 PLUMBING - FINAL Approved IVRS - Inspection 0000* R.O. UNIT HAS BEEN REMOVED. PLUMBER TO INSTALL PROPER CO FOR K SINK
07/01/2003 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection 0000*
06/30/2003 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection 0000*/ 1) NOT READY ON RO-ALSO PROVIDE ACCESS TO CLEANOUT
06/29/2003 PLUMBING - FINAL Denied IVRS - Inspection 0999*/ 1) PLEASE READ NOTE #2-ABOVE. THE DRAIN MAY NOT BE DIRECTLY CONNECTED TO WASTE PIPING BESIDES SLIP NUT EXTENSION TAIL PIECE IS NOT APPROVED IN THE HORIZONTAL POSITION; IT IS NOT A DRAINAGE FITTING
06/25/2003 PLUMBING - FINAL Denied IVRS - Inspection 0999*/ 1) ABS MAY NOT BE TAPPED OR THREADED TO MAKE A CONNECTION 2) R.O. DRAIN MAY NOT BE DIRECTLY CONNECTED TO WASTE PIPING. THIS IS CONSIDERED A CROSS CONNECTION
06/24/2003 PLUMBING - FINAL Denied IVRS - Inspection 0999* DOOR LOCKED NO ACCESS