Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T02CM05745
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/01/2003 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection 0000* | |
| 03/26/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*1.) FINISH FIRE PLACE OK TO INSULATE AND ROCK EXCEPT AS NOTED. | |
| 03/24/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*FILL UNUSED OPENING IN PANEL 2.) FINISH WIRING TO FIRE PLACE. |
|
| 03/11/2003 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection 0999* 1.) CABLES TO BE SECURED TO PANEL AND NOT BONDING ALSO SUPPORT CABLES ABOVE PANEL. USE APPROVED CONNECTORS 370-17,370-5. 2.) CABLES TO BE SECURED TO BOXES USE AN APPROVED CONNECTOR 370-17, 373-5. 3.) PLEASE PROVIDE GROUND TAILS FOR SWITCHES ON ROUGH ELECTRIC. 4.) A BOX MAY BE NEEDED FOR BATH LIGHT. 5.) USE AN APPROVED CONNECTOR AT EXHAUST FANS 370-17, 373-5. 6.) CABLES TO BE STRAPPED WITHIN 12" OF BOXES & CANS 336-18. 7.) GROUND METAL BOXES AND INSTALL 3/4 OF A TURN IN A CLOCKWISE DIRECTION. 8.) PROTECT CONDUCTORS INSIDE OF BOXES WITH SCREWS 370-43. |