Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T02CM05745

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
04/01/2003 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection 0000*
03/26/2003 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*1.) FINISH FIRE PLACE OK TO INSULATE AND ROCK EXCEPT AS NOTED.
03/24/2003 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*FILL UNUSED OPENING IN PANEL
2.) FINISH WIRING TO FIRE PLACE.
03/11/2003 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0999*
1.) CABLES TO BE SECURED TO PANEL AND NOT BONDING ALSO SUPPORT CABLES ABOVE PANEL. USE APPROVED CONNECTORS 370-17,370-5.
2.) CABLES TO BE SECURED TO BOXES USE AN APPROVED CONNECTOR 370-17, 373-5.
3.) PLEASE PROVIDE GROUND TAILS FOR SWITCHES ON ROUGH ELECTRIC.
4.) A BOX MAY BE NEEDED FOR BATH LIGHT.
5.) USE AN APPROVED CONNECTOR AT EXHAUST FANS 370-17, 373-5.
6.) CABLES TO BE STRAPPED WITHIN 12" OF BOXES & CANS 336-18.
7.) GROUND METAL BOXES AND INSTALL 3/4 OF A TURN IN A CLOCKWISE DIRECTION.
8.) PROTECT CONDUCTORS INSIDE OF BOXES WITH SCREWS 370-43.