Permit: T02CM05739

Parcel: 112050650


Addresses:

3026 N CAMPBELL AV

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Date Description Inspector Results Comments
07/15/2003 ELECTRIC - ABOVE CEILING Approved
06/30/2003 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection 0000*
06/23/2003 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection 0000*/ 1) PLEASE PROVIDE LETTER VERIFYING TORQUEING OF EQUIPMENT 2) WE HAVE A MANUFACTURE LABEL STATING 2 LUGS PER PHASE WE HAVE 3 PER PHASE 3) PLEASE INSTALL REJECTION PINS AT SERVICE DISCONNECTS 4) AN ADDRESS LABEL IS NEEDED AND LABEL DISCONNECTS 5) APPROVED EXTENDER RINGS WILL BE NEEDED FOR BOXES MORE THAN 1/4" TO SURFACE-METAL NOT APPROVED 6) TEMP POWER FOR TEST AND ALL BOXES BELOW 8' MUST BE PLATED OR DEVICE INSTALLED 7) FINISH BOX MAKE-UP KITCHEN IN CEILING
05/21/2003 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection 0000*
05/20/2003 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection 0000* HARD LIDS OK. ROUGH IN OK