Permit: T02CM05739

Parcel: 112050650


Addresses:

3026 N CAMPBELL AV

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
07/15/2003 ELECTRIC - INTERMEDIATE Approved
05/02/2003 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*
SUPPORT CONDUITS ABOVE CONTROL PANEL WITHIN 3'
2.) SUPPORT M/C CABLE WITHIN 12" OK WALLS.
04/30/2003 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0920*GATES LOCKED NO ACCESS 2:45PM.
04/28/2003 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0245*MC CABLE TO BE SUPPORT WITHIN 12" EACH TERMINATION AND AT 6' INTERVALS PER NEC.
2.) INSULATE FROM COPPER WATER LINES.
3.) LETTER FROM ARCH VERIFY USE OF MC CABLE.
03/18/2003 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*1.) PLEASE ADD 2010 TO PERMIT.
2.) WHAT IS 6TH CONDUIT FOR?
3.) OK 6-21/2" PVC CONDUIT FOR PANELS UNDER SLAB.
4.) OK 1-2" PVC CONDUIT FOR PHONE UNDER SLAB.