Permit: T02CM05734

Parcel: 13316030E

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
02/03/2003 ELECTRIC - FINAL Approved IVRS - Inspection 0000*OK FINAL.
01/31/2003 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*1.) A MANUFACTURES APPROVED TIE HANDLE IS NEEDED FOR TWO POLE BREAKER NO COPPER WIRE.
2.) GROUND METAL BOXES AS PER 517-13 (#3 PREVIOUS INSPECTION.)
01/10/2003 ELECTRIC - FINAL Denied IVRS - Inspection 0999*1. FIXTURES TO BE SUPPORTED AS PER CODE. 410-16 AND CITY/AMEDMENTS. 2 WIRES IN OPPSITE DIRECTION AND ATTACHED TO GRID.
2.)WHAT IS OUTLET IN CEILING FOR 3 NEED AN APPROVED EXTENDER RING FOR MORE THAN 1/4" FROM BOX TO DEVICE IN COMBUSTABLES
3.) PLEASE VERIFY GROUNDING OF RECEPTACLES AS PER 517-13.
4.) WE ARE MISSING DEVICE COVERS.
5.) PLEASE VERIFY LISTINGS FOR NEW PUMPS.
6.) COULD NOT ACCESS PANEL. PLEASE PROVIDE AND MAINTAIN WORKING CLEARENCES AS PER 110-26.
7.) PLEASE OPEN UP ALL TILES FOR ACCESS.