Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 05/27/2004 |
MECHANICAL - FINAL |
|
Approved |
IVRS - Inspection :* |
| 03/11/2004 |
MECHANICAL - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000* |
| 02/27/2004 |
MECHANICAL - FINAL |
|
Partial Approval |
IVRS - Inspection 0000* |
| 04/02/2003 |
MECHANICAL - FINAL |
|
Denied |
IVRS - Inspection 0999* |
| 04/01/2003 |
MECHANICAL - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000* |
| 12/13/2002 |
MECHANICAL - FINAL |
|
Denied |
IVRS - Inspection 0999*/ 1) ROOF ON THIS HOUSE HAS BEEN REPLACED WITHOUT INSPECTION OR APPROVAL. 2 X 4 RAFTERS ARE INSTALLED AT 48" ON CENTER. PROVIDE CITY OF TUCSON APPROVED ROOF PLAN AND MAKE REPAIRS 2) DUCT TRANSITION ON EAST SIDE OF HOUSE ARE NOT INSULATED REQUIRE R-6 MINIMUM 3) DUCT BROKEN, IMPROPER SPLICE AT LIVING ROOM 4) GAS LINE MISSING ROOF JACKS 5) NO ELECTRIC DATA PLATE/LABEL A/C UNIT 6) A/C GROUND NOT PROPERLY COLOR CODED MUST BE GREEN 7) NO CONDENSATE DRAIN OR TRAP ON A/C 8) ELECTRIC JUNCTION BOXES CANNOT BE CONCEALED IN CAVITIES |