Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T02CM05717
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/27/2004 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 03/11/2004 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection 0000* | |
| 02/27/2004 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection 0000* | |
| 04/02/2003 | MECHANICAL - FINAL | Denied | IVRS - Inspection 0999* | |
| 04/01/2003 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection 0000* | |
| 12/13/2002 | MECHANICAL - FINAL | Denied | IVRS - Inspection 0999*/ 1) ROOF ON THIS HOUSE HAS BEEN REPLACED WITHOUT INSPECTION OR APPROVAL. 2 X 4 RAFTERS ARE INSTALLED AT 48" ON CENTER. PROVIDE CITY OF TUCSON APPROVED ROOF PLAN AND MAKE REPAIRS 2) DUCT TRANSITION ON EAST SIDE OF HOUSE ARE NOT INSULATED REQUIRE R-6 MINIMUM 3) DUCT BROKEN, IMPROPER SPLICE AT LIVING ROOM 4) GAS LINE MISSING ROOF JACKS 5) NO ELECTRIC DATA PLATE/LABEL A/C UNIT 6) A/C GROUND NOT PROPERLY COLOR CODED MUST BE GREEN 7) NO CONDENSATE DRAIN OR TRAP ON A/C 8) ELECTRIC JUNCTION BOXES CANNOT BE CONCEALED IN CAVITIES |