Permit: T02CM05705

Parcel: 115190310


Addresses:

1693 W GRANT RD

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
06/27/2003 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection 0000*
05/27/2003 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*/ 1) PLEASE CORRECT THE FOLLOWING: AT THE MAIN SWITCH LOCATED OUTSIDE. PLEASE ADD GROUNDING BUSHING TO NIPPLE IN THE SWITCH AND A GROUNDING LOCKNUT IN THE GUTTER. A GROUNDING BUSHING IS NEEDED DUE TO THE CONCENTRIC KO'S. BE SURE TO MARK YOUR DISCONNECTS AT BOTH ENDS-INSIDE AND AT SERVICE