Permit: T02CM05700

Parcel: 11704058B


Addresses:

401 E 5TH ST


Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T02CM05700

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
08/04/2003 PLUMBING - FINAL Approved IVRS - Inspection 0000*/ 1) PLUMBING FINAL OK. 2) OK FOR C OF O PENDING ANY OTHER INSPECTIONS. 3) HAVE LAST INSPECTOR LEAVE GAS CARD.
07/31/2003 PLUMBING - FINAL Denied IVRS - Inspection 0999*/ 1) ICE MAKER AND ICE BIN DRAINS ARE GOVERNED BY 94 UPC. THEY MUST BE PIPED IN A SPECIFIC MANNER IN ORDER TO AVOID NUMEROUS HEALTH RISKS. HAVE PLUMBER PIPE THEM CORRECTLY AND RECALL FOR INSPECTION
07/30/2003 PLUMBING - FINAL Denied IVRS - Inspection 0999*/ 1) ALL FIXTURES TO BE CAULKED 2) ICE MAKER MUST HAVE AIR BREAK OR RPPBP BACKFLOW PROTECTION 3) ICE MAKER AND ICE BIN TO BE DRAINED SEPERATELY PER 94 UPC 4) CLEANOUT COVER ON FLOOR A TRIPPING HAZARD 5) INTERMINGLY OF ABS AND PVC NOT APPROVED 6) TRAP TO BE SAME SIZE AS TRAP ARM 7) SEAL VOID AROUND GAS PIPE PENETRATION
07/28/2003 PLUMBING - FINAL Denied IVRS - Inspection 0999*