Permit: T02CM05650

Parcel: 13316004E

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
02/19/2003 MECHANICAL - FINAL Approved IVRS - Inspection 0000*OK FOR C OF O.
02/14/2003 MECHANICAL - FINAL Denied IVRS - Inspection 0935*CORRECTIONS HAVE NOT BEEN MADE ON CONDENSATE TRAPS. PAY A RE-INSPECTION FEE PRIOR TO NEXT INSPECTION.
2.) FINISH INSTALLING REFRIGERATION EQUIPMENT OK FOR TEMP C OF O.
02/12/2003 MECHANICAL - FINAL Partial Approval IVRS - Inspection 0000*1.) VENTS ON CONDENSATE DRAIN TRAPS MUST BE DOWNSTREAM OF THE TRAP FINISH CONNECTION TO 5 TON CARRIER UNIT.2.) BE SURE KITCHEN EXHAUST FANS HAVE GREASE CUPS. RECALL FOR INSPECTION.
01/29/2003 MECHANICAL - FINAL Partial Approval IVRS - Inspection 0000*BRING CONDENSATE DRAIN LINE UP TO CODE PAINT EXPOSED PVC W/LATEX PAINT.
BLOCK & CLAMP PVC MAX. 4' INTERVALS.
PROVIDE ADEQUATE SLOPE
RECONNECT TO EQUIPMENT AS NEEDED RECALL FOR INSPECTION.
01/09/2003 MECHANICAL - FINAL Partial Approval IVRS - Inspection 0000*