Permit: T02CM05650

Parcel: 13316004E

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
05/02/2003 ELECTRIC - FINAL Approved IVRS - Inspection 0000*OK FINAL.
05/01/2003 ELECTRIC - FINAL Denied IVRS - Inspection 0920*LOCKED NO ACCESS.
04/10/2003 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection 0000*FINISH PREVIOUS INSPECTIONS.
04/03/2003 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*1.) PLEASE VERIFY LIGHTING ON FRONT POLES OR INSTALL AS PER LIGHTING CODES.
2.) LOW VOLTAGE ON ROOF TO BE INSTALL WITH APPROVED WIRING METHODS AS PER CODE.
BACK LOT LIGHTING OK
02/14/2003 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*1.) SEALTITE TO A/C UNITS TO HAVE A FITTING AND STRAPED.
2.) YOU HAVE 30 DAY TO COMPLY WITH LIGHTING CODES ITEM #10 PREVIOUS INSPECTION. OK TEMP C OF O.
02/12/2003 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*
02/05/2003 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*1.) FINISH WALK IN COOLERS.
1.) ROOF STILL HAS EXPOSED CONDUCTOR IN SEAL TITE LAYING ON ROOF AND EXPOSED GTO CABLE.
3.) FINISH ITEM 4,5,6,9 & 10 OF PREVIOUS INSPECTION.
01/29/2003 ELECTRIC - FINAL Denied IVRS - Inspection 0999*1.) PLEASE REMOVE EMPTY CONDUIT BACK TO SERVICE SECTION OR SEAL.
2.) REPLACE MISSING GUTTER SECTION COVER.
3.) PLEASE LABEL PANEL COVERS ON OUTSIDE OF COVER.
4.) RE PLACE MISSING COVER PLATES IN COOLER AND TERMANATE SEALTITE CONDUIT ENDS OR REMOVE.
5.) PLEASE TERMANATE SEALTITE CONDUIT ENDS OR REMOVE.
6.) EXTENDER RINGS WILL BE NEEDED WHERE MORE THAN 1/4" FROM BOX TO DEVICE METAL NO APPROVED.
7.) A DEADFRONT COVER IS NEEDED AT PANEL IN KITCHEN
8.) INSTALL ALL MISSING COVER PLATES.
9.) NEED TO SEE KITCHEN EQUIPMENT TO VERIFY LISTING/LABELS
10.) OUT DOOR LIGHTING TO MEET LIGHTING CODES REINSTALL WALL PACK.
11.) WE HAVE EXPOSED CONDUCTORS AT DISCONNECT ON ROOF AND LAYING ON ROOF ALSO FITTING LOOSE AND DETACHED FROM DISCONNECT.