Permit: T02CM05618

Parcel: 109250200

Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Date Description Inspector Results Comments
06/20/2003 PLUMBING - ROUGH, SOIL Approved
06/19/2003 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection 0999*
01/31/2003 PLUMBING - ROUGH, SOIL Partial Approval 1.) SK DRAWING REVISED NOW SHOWS 3" BLDG DRAIN.
2.) PLUMBING INSTALLED PER APPROVED REVISED PLAN WITH EXCEPTION AT TOILET RM #108. HORIZONTAL VENT NOT NECESSARY
3.) OK TO COVER ALL AREAS EXCEPT RM #108.
4.) WATER TEST ONE RISER TO TEN FEET.
01/27/2003 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection 0000*SORRY
SEE PLUMBING KEY NOTES #3. THEN HAVE YOUR PLUMBER LOOK ON P-1 LINE DRAWING WITH #3 3" HAS BEEN INSTALLED. PLANS CALL FOR 4" ALSO SEE TOILET ROOM #108. 3" STUB UP IN WALL & WHY FLAT VENT ON WC FOR TOILET ROOM #108 SEE RISER DIAGRAM? CONDENSATE TRAP DETAIL.
01/16/2003 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection 0000*