Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - YARD WTR LINE/TEST
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/12/2003 | PLUMBING - YARD WTR LINE/TEST | Approved | 1.) SEE NOTE #03 FROM 2/6/03. 2.) REQUIRED ONE INCH CLEARANCE FOR DOUBLE WALL FROM COMBUSTIBLES 3.) REMOVE UNIONS SEE 1211.10 94 UPC CONCERNING UNIONS 4.) SEE 313.8 94 UPC WATER PROOFING OF OPENINGS USE APPROVED FLASHING. 5.) YARDWATER CONNECTIONS MADE OK OK TO COVER. |
|
| 02/06/2003 | PLUMBING - YARD WTR LINE/TEST | Denied | 1.) SEE 606.2.2 94UPC FEMALE PVC SCREWED FITTINGS ON WATER PIPING ARE PROHIBITED. 2.) PVC WATER PIPING INSTALLED ABOVE GRADE NOT ADVISED 3.) PLEASE PROVIDE GAS ISOMETRIC (APPROVED) SHOWING DEVELOPED LENGTH AND BTU CONSUMPTION. 4.) ALL ROOF PENETRATIONS REQUIRE APPROVED FLASHINGS. 5.) FLEX CONNECTOR NOT PERMITTED ON T & P RELIEF DRAIN. 6.) PROVIDE MINIMUM 10# AIR TEST ON GAS SYSTEMS DO NOT TEST THROUGH APPLIANCES. |