Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 02/12/2003 |
ELECTRIC - INTERMEDIATE |
|
Approved |
IVRS - Inspection 0000* |
| 02/06/2003 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000*/ CORRECTIONS REQUIRED: 1) A COMPLETE NEW GROUNDING SYSTEM MUST BE INSTALLED. EXISTING " UNPROVEN " GROUND IS NOT ACCEPTABLE 2) SEPERATE EACH PANEL FROM THE OTHER BY REMOVING THE 1/2" EMT COMMON CONNECTION TO BELL BOX ABOVE PANEL 01. EACH PANELS CIRCUITS MUST NOT MIX WITH THE OTHER 3) RECEPTACLES MOUNTED AT FLOOR LEVEL AND SLIGHTLY BELOW DO NOT MEET SAFETY REQUIREMENTS OF ARTICLE 410-57(B)(Z) AND 410-57(D). |