Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/24/2003 | MECHANICAL - FINAL | Approved | IVRS - Inspection 0000* | |
| 04/08/2003 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection 0000* 1.) PVC CONDENSATE PIPING, EXPOSED TO RUN, NEEDS TO BE PAINTED W/LATEX PAINT. 2.) PVC PIPING AND ELECT. HI VOLTAGE PENTRATONS AT ROOF SURFACE NEED TO E IN FLASHING, TEE TOPS. NOTE!! PROVIDE A COPY OF THIS TO CONTRACTOR SO THIS JOB CAN BE COMPLETED, ALL ADDITIONAL STEPS. JOB LOOKING MUCH BETTER. |
|
| 04/04/2003 | MECHANICAL - FINAL | Not ready for Inspection | 1.) PAINT ALL EXPOSED PVC W/LATEX PAINT. 2.) PROVIDE ROOF JACKS WHERE ELECTRICAL GAS & CONDENSATE PIPES PENETRATE THE ROOF. RECALL FOR INSPECTION. |
|
| 03/12/2003 | MECHANICAL - FINAL | Denied | IVRS - Inspection 0999*HAVE CONTRACTOR MECHANICAL CALL ME! ITEMS CONDENSATE PVC TRAP. EXPOSED UNINSULATED DUCT WORK ON ROOF. |