Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/22/2003 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000*OK FINAL | |
| 05/12/2003 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*PLEASE FINISH #2 OF PREVIOUS INSPECTION. | |
| 05/06/2003 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*1.) FINISH CONNECTIONS AT JUNCTION BOXES. 2.) WE NOW HAVE DATA CABLE LAYING CEIL GRID THAT WAS NOT INSTALLED ON PREVIOUS INSPECTION PLEASE SUPPORT. 3.) FINISH INSTALLATION OF UNDER CABINET LIGHTING OK CONDUIT AT PULL BOX IN PARKING LOT. |
|
| 05/01/2003 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*OK TEMP C OF O SUBJECT TO BOND. APPROVED CONNECTORS ARE NEEDED FOR CABLES 2.) FINISH SUPPORTING M/C CABLE TO CANS 3.) CORRECT BURIAL DEPTH FOR CONDUITS IN PARKING LOT IS NEEDED AS PER ITEM FOR CONDUIT DATED 4-16-03. |
|
| 04/30/2003 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*OK ROOF OK SERVICE. 1.) FINISH ITEM #3 OF INSPECTION DATED 4-29-03. 2.) FINISH ITEM FOR CONDUIT IN PARKING LOT DATED 4-16-03. |
|
| 04/29/2003 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999*1.) FIXTURES BOX TO BE ATTACHED TO GRID 410-16. 2.) M/C CABLE TO BE SUPPORTED AS PER CODE. 3.) FINISH INSTALLATION OF UNDER LIGHTING & CEILING LIGHTS. 4.) BOXES TO BE GROUNDED 250-148. 5.) ATTACH BOXES SECURLY TO STRUCTURE. 6.) WE HAVE EXPOSED CONDUCTOR AT BATH LIGHT, ALSO PROTECT CONDUCTORS ENTERING FIXTURES. ROOF . 1.) TIGHTEN SEALTITE FITTINGS. 2.) INSTALL STANDED CONDUCTORS CORRECTLY UNDER LUGS. 3.) IDENIFY A/C UNITS. 4.) GROUND WALL LIGHT BOXES AND BRING BOX OUT PER 370-20. |