Permit: T02CM05613

Parcel: 12511055A


Addresses:

1001 N ALVERNON WY

Inspection Status: Approved

Inspection History: ELECTRIC - CABLE DROP

Date Description Inspector Results Comments
04/29/2003 ELECTRIC - CABLE DROP Approved IVRS - Inspection 0000*
04/28/2003 ELECTRIC - CABLE DROP Partial Approval IVRS - Inspection 0000*
1.) FIXTURE CLIPS TO BE EFFECTIVE.
2.) TIGHTEN LOOSE M/C CONNECTORS
3.) WHEN USING SUPPORT WIRES THEY ARE TO BE ATTACHED AT BOTH ENDS 300-11.
4.) SUPPORT ALL WIRES UP OFF OF GRID.
OK ABOVE CEILING EXCEPT RM #101,102,103,104,112,113,114, HALL 5 121,122,106.
SERVICE
1.) BONDING JUMPERS TO BE SIZED PER 250-102 & 250-66.
2.) CAN NOT STACK LUGS.
3.) FINISH TERMANATIONS OF CONDUCTORS.
TEMP POWER FOR TEST
1.) CAP ALL CONDUCTORS BELOW 8'.