Inspection History: ELECTRIC - CABLE DROP
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/29/2003 | ELECTRIC - CABLE DROP | Approved | IVRS - Inspection 0000* | |
| 04/28/2003 | ELECTRIC - CABLE DROP | Partial Approval | IVRS - Inspection 0000* 1.) FIXTURE CLIPS TO BE EFFECTIVE. 2.) TIGHTEN LOOSE M/C CONNECTORS 3.) WHEN USING SUPPORT WIRES THEY ARE TO BE ATTACHED AT BOTH ENDS 300-11. 4.) SUPPORT ALL WIRES UP OFF OF GRID. OK ABOVE CEILING EXCEPT RM #101,102,103,104,112,113,114, HALL 5 121,122,106. SERVICE 1.) BONDING JUMPERS TO BE SIZED PER 250-102 & 250-66. 2.) CAN NOT STACK LUGS. 3.) FINISH TERMANATIONS OF CONDUCTORS. TEMP POWER FOR TEST 1.) CAP ALL CONDUCTORS BELOW 8'. |