Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 10/24/2003 |
BUILDING - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 10/17/2003 |
BUILDING - FINAL |
|
Denied |
IVRS - Inspection 0999* 1) WATER HEATER SINGLE WALL TO DOUBLE WALL VENT CONNECTION MUST BE WITH 3 SCREWS. NO TAPE. 2) WATER HEATER TEMP & PRESSURE RELIEF LINE MUST HAVE A CONTINUOUS DOWN FLOW. NO LOOP AND CANNOT USE CORRIGATES COPPER ON T & P LINE. RIGID ONLY. SUPPLY LINES OK. 3) SUPPORT FURNACE GAS LINE TO PREVENT BREAKAGE. 4) INSTALL BOND JUMPER ON A/C FLEX BOOT.5) ALL OUTSIDE ELECTRIC OUTLETS MUST BE GFCI PROTECTED- AND WORK.6) KITCHEN COUNTER OUTLETS MUST BE GFCI PROTECTED. 7) BARE BULB LIGHT TIXTURES NOT ALLOWED IN CLOSET. |