Permit: T02CM05601

Parcel: 120031580

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Date Description Inspector Results Comments
10/24/2003 BUILDING - FINAL Approved IVRS - Inspection 0000*
10/17/2003 BUILDING - FINAL Denied IVRS - Inspection 0999* 1) WATER HEATER SINGLE WALL TO DOUBLE WALL VENT CONNECTION MUST BE WITH 3 SCREWS. NO TAPE. 2) WATER HEATER TEMP & PRESSURE RELIEF LINE MUST HAVE A CONTINUOUS DOWN FLOW. NO LOOP AND CANNOT USE CORRIGATES COPPER ON T & P LINE. RIGID ONLY. SUPPLY LINES OK. 3) SUPPORT FURNACE GAS LINE TO PREVENT BREAKAGE. 4) INSTALL BOND JUMPER ON A/C FLEX BOOT.5) ALL OUTSIDE ELECTRIC OUTLETS MUST BE GFCI PROTECTED- AND WORK.6) KITCHEN COUNTER OUTLETS MUST BE GFCI PROTECTED. 7) BARE BULB LIGHT TIXTURES NOT ALLOWED IN CLOSET.