Permit: T02CM05591

Parcel: 12216026B


Addresses:

3670 E GRANT RD

Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Date Description Inspector Results Comments
02/13/2003 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection 0000*1.) SOIL WATER TEST IS OK
2.) P.O.C. OF NEW BLDG DRAIN TO EXSISTING BLDG. DRAIN IS OK
3.) OVERHEAD WATER DISTRIBUTION IS OK
4.) OK TO BACKFILL TRENCH.
02/06/2003 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection 0999*UNABLE TO COMPLETE INSPECTION.
#1. PLUMBING CONTRACTOR TO BE ON JOB AT TIME OF INSP. DO NOT COVER WORK TO BE INSPECTED.
#2. PLEASE PROVIDE LINE DRAWING OR ISOMETRIC DRAWING WITH SIZE OF WASTE LINES.
#3. PLEASE PROVIDE LIST OF SUBS FOR OUR OFFICES.
02/05/2003 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection 0000*1.) PLEASE POST ADDRESS WHERE IT CAN BE SEEN FROM THE STREET
2.) HAVE ARCHETECT COMPLETE THE PLUMBING PLAN AND HAVE IT STAMPED. BY THE PLANS EXAMINER I.E. SIZES OF DRAINS, DRAW IN THE PLUMBING FOR THE LAVATORY, AND AS BUILT ROUTING OF BLDG DRAIN.
3.) THE AGGREGATE CROSS SECTIONAL AREA OF VENTING DOES NOT EQUAL THE MAXIMUM REQUIRED BLDG. SEWER AREA.
4.) THERE APPEARS TO BE A LEAK AT THE 4" CONECTION TO EXISTING.
5.) REMOVE DIRT AND DEBRIS FROM AROUND PIPE AND FITTINGS SO PROPER INSPECTION MAY BE MADE.