Inspection Status: Approved
Inspection History: FRAMING
| Date |
Description |
Inspector |
Results |
Comments |
| 04/24/2003 |
FRAMING |
|
Approved |
IVRS - Inspection 0000* |
| 04/04/2003 |
FRAMING |
|
Not ready for Inspection |
IVRS - Inspection 0000*/ 1) BLOCK IN OPENING NORTH SIDE BLOCKWALL 2) INSTALL SOLID 2 X 8'S BETWEEN RAFTERS ABOVE BLOCK WALL NORTH SIDE AND 2' RETURN EACH END 3) MAINTAIN FULL BEARING RAFTERS AT BEARING (4 X6'S) 4) FILL ALL NAIL HOLES H2.5 CLIPS 5) INSTALL 4TH WIRE (NETRAL) WHITE FROM MAIN TO SUB-PANEL 6) INSTALL 2 X 4 TO BEEF UP 1/2" ROOF DECK BETWEEN EXITING (SPAN INDEX MAXIMUM 34 1/2") 7) INSTALL SEPARATE 30 AMP BREAKER MAIN PANEL 8) SEPARATE NEUTRALS AND GROUNDS AT SUB-PANEL |