Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T02CM05572
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/05/2003 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* | |
08/04/2003 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*/ 1) WHEN SUPPORTING ELECTRIC II IS TO BE SUPPORTED AS PER 300-11 ATTACHED AT BOTH ENDS 2) PLEASE ATTACH FIXTURES TO GRID 410-16 3) A GROUNDING ELECTRODE IS NEEDED FOR SEPARATELY DERIVED SYSTEM AT TRANSFORMER 4) FINISH LABELING PANELS ON COVER AND CIRCUIT DIRECTORIES 5) CLEAN SURFACE UNDER LUG IN TRANSFORMER AND INSTALL MAIN BONDING JUMPER 6) FINISH ELECTRIC INSTALLATIONS 7) LIGHTING DOES NOT MATCH PLANS PLEASE PROVIDE AN APPROVED REVISED PLAN |