Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T02CM05524
Inspection Description - FRAMING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/18/2003 | FRAMING | Approved | IVRS - Inspection 0000* | |
12/17/2003 | FRAMING | Partial Approval | IVRS - Inspection 0000*/ 1) WILL REINSPECT AFTER PUMBING APPROVAL | |
10/13/2003 | FRAMING | Denied | IVRS - Inspection 0999*/ 1) TUB AND LAUNDRY WATER CLOSET TRAP WEIRS ARE HIGHER THAN VENT OPENINGS MUST USE SANITARY "T" CONNECTIONS NOT COMBOS 2) FOUNDATION IS NOT PER PLAN. PRESENTLY SITTING ON WOOD FOUNDATION BUILD TO PLAN OR REVISE PLAN TO AS BUILT 3) HAVE ARCHITECT INCORPORATE LETTER DETAIL INTO PLAN 4) PROVIDE PLAN DETAIL FOR POST/BEAM CONNECTION TO EXISTING FOUNATION 5) REDUCE GAS LINES AT DROPS ONLY 6) GAS LINE MUST BE ELECTRICALLY BONDED 7) GROUND ALL METAL ELECTRIC BOXES 8) BEDROOM WALL BEARING CEILING SITTING ON 2 X 6 FLOOR JOIST 9) FIREBLOCK THROUGHOUT 10) INSULATE ALL DUCT Y'S WITH R-6 11) REAR PORCH SHEATHING OK TO COVER 12) PORCH ALL BUT CLOSET OK TO COVER | |
10/03/2003 | FRAMING | Not ready for Inspection | IVRS - Inspection 0000*/ 1) CANCELLED | |
09/09/2003 | FRAMING | Denied | IVRS - Inspection 0999* | |
09/05/2003 | FRAMING | Not ready for Inspection | IVRS - Inspection 0000* | |
09/03/2003 | FRAMING | Not ready for Inspection | IVRS - Inspection 0000*/ 1) NOT READY, CANCELLED 2) HAVE #46 ADDRESS PUT ON HOUSE AND #48 REMOVED |