Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T02CM05523
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/12/2002 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection 0000* | |
12/11/2002 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection 0999*/ 1) BASE BOARD HEATER MUST BE ON A DEDICATED CIRCUIT. UNABLE TO DETERMINE SUB PANEL NOT LABELED 2) ELECTRIC SUB PANEL HAS 3-20 AMP BREAKERS SERVING 14 GUAGE WIRES. MUST BE 15 AMP BREAKERS 3) LABEL ALL CIRCUITS IN SUB PANEL 4) PROVIDE PANEL DEAD FRONT (COVER) 5) EXPOSED WIRES AT SUB PANEL MUST BE PHYSICALLY PROTECTED 6) NEUTRAL WIRE MUST BE WHITE-COLOR CODE 7) ANCHOR ISOLATED BAR |