Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 07/17/2003 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000*/ 1) OK FINAL |
| 07/15/2003 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*/ 1) TIGHTEN LOOSE FITTINGS 2) WE HAVE AN UNSAFE CONDITION IN BACK CLASS ROOM WITH THE CEILING FAN AND EXPOSED NM CABLE 3) PLEASE PROVIDE A REVISE PANEL SCHEDULE 4) FUSE TO BE LPN-RR FOR FAULT CURRENT LET THROUGH 5) TIGHTEN LOOSE SEAL TITE FITTINGS AT A/C |
| 07/09/2003 |
ELECTRIC - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000*/ ELECTRICIAN NOT FINISHED. A RE FEE MAY BE ASSESSED IF NOT READY ON NEXT INSPECTION. |
| 07/08/2003 |
ELECTRIC - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000* |