Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
08/29/2003 MECHANICAL - FINAL Approved IVRS - Inspection 0000*/ CORRECTIONS HAVE BEEN MADE. OK FOR C OF O.
08/20/2003 MECHANICAL - FINAL Partial Approval IVRS - Inspection 0000*/ MAX. FUSE SIZE - OUTSIDE SECTION - 40 AMPS. / UNIT CIRCUIT BREAKER AT SERVICE - 50 AMPS. / AIR HANDLER 5K WITH AUX HT STRIP. FUSES 30 AMP MAX., NOT 50.