Permit: T02CM05480

Parcel: 133369570


Addresses:

60 N HARRISON RD

Inspection Status: Approved

Inspection History: ELECTRIC - CABLE DROP

Date Description Inspector Results Comments
09/04/2003 ELECTRIC - CABLE DROP Approved IVRS - Inspection 0000* SENT TO TEP ON 0905AM
09/02/2003 ELECTRIC - CABLE DROP Partial Approval IVRS - Inspection 0000*/ 1) BONDING ON LINE SIDE CONDUITS TO BE AS PER 250.102/250.66 2) USE LUGS APPROVED FOR CONDUCTOR SIZED 3) PLEASE PROVIDE LETTER FOR TORQUE