Inspection History Details
Inspection Status: Approved
Inspection History: EXT METAL CLIPS/EXT SHEATHING
Permit Number - T02CM05469
Inspection Description - EXT METAL CLIPS/EXT SHEATHING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/29/2003 | EXT METAL CLIPS/EXT SHEATHING | Approved | ||
01/27/2003 | EXT METAL CLIPS/EXT SHEATHING | Partial Approval | 1) RETRO FIT H.D. IS NOT NAILED TO STUDS INTER SECTING WALL CONNECTION TO BE DONE LIKE 10/SD4, H.D. OUTSIDE OF WALL, ALL SHEAR WALLS 2) PUT OSB BEHIND DRYER DUCT FOR HT OF CHASE 16D 12" ON CENTER VERTICAL 3) BLOCK EDGES | |
01/22/2003 | EXT METAL CLIPS/EXT SHEATHING | Partial Approval | IVRS - Inspection 0000*/ 1) LATERAL BRACES 2) NAIL OFF ALL SHEAR PANELS 3) NEED RETRO FINT P.A. FOR MISSED STRAP ON EAST SIDE 4) STUD LOOSE AT BOTTOM PLATE GARAGE EAST MISSING A.B. | |