Permit: T02CM05425


Addresses:

1420 S ALVERNON WY


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T02CM05425

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
11/26/2002 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
11/25/2002 ELECTRIC - FINAL Denied IVRS - Inspection 0245*2 X 4 LAYIN FIXTURES REQUIRE SEISMIC WIRES AT CADDY CORNERS. THE CLIPS (4) MUST BE TURNED OUT TO ENGAGE THE GRID OR THEY MUST BE SCREWED TO THE GRID WITH 2 SHEET METAL SCREWS ONE AT EACH END.
2.) THE ELECTRICAL PANELS REQUIRE BLANK PLATES TO COVER UNUSED CIRCUIT BREAKER POSITIONS.
3.) THERE IS AN OPEN 'J 1 BOX AT THE NORTH EAST CORNER. ABOVE RESTROOM DOOR. INSTALL A BLANK COVER ON IT.
4.) INSTALL A GROUND WIRE FROM THE PULL OUT TO THE A/C UNIT TO GROUND THE CABINET USE HACR RATED FUSES.