Inspection History: ELECTRIC - FINAL
Permit Number - T02CM05425
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/26/2002 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* | |
11/25/2002 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0245*2 X 4 LAYIN FIXTURES REQUIRE SEISMIC WIRES AT CADDY CORNERS. THE CLIPS (4) MUST BE TURNED OUT TO ENGAGE THE GRID OR THEY MUST BE SCREWED TO THE GRID WITH 2 SHEET METAL SCREWS ONE AT EACH END. 2.) THE ELECTRICAL PANELS REQUIRE BLANK PLATES TO COVER UNUSED CIRCUIT BREAKER POSITIONS. 3.) THERE IS AN OPEN 'J 1 BOX AT THE NORTH EAST CORNER. ABOVE RESTROOM DOOR. INSTALL A BLANK COVER ON IT. 4.) INSTALL A GROUND WIRE FROM THE PULL OUT TO THE A/C UNIT TO GROUND THE CABINET USE HACR RATED FUSES. |