Inspection History Details
Inspection Status: Approved
Inspection History: EXT METAL CLIPS/EXT SHEATHING
Permit Number - T02CM05423
Inspection Description - EXT METAL CLIPS/EXT SHEATHING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/03/2003 | EXT METAL CLIPS/EXT SHEATHING | Approved | IVRS - Inspection 0000* | |
12/31/2002 | EXT METAL CLIPS/EXT SHEATHING | Not ready for Inspection | IVRS - Inspection 0000*/ 1) NAIL OFF DRAG STRUTS MARKED ON ROOF DECK 2) STRUCTURE ISN'T BRACES (IT'S VERY SHAKEY) 3) NEED WIND BRACING AT FRONT WALL 2ND FLOOR 4) ALL WIND BRACES TO HAVE 2 16D'S AT PLATES 5) INSTALL 2ND FLOOR H.D. DETAIL EACH END OF WALL 18-10-16/SD4 6) NAIL PANEL TO FLOOR AND NAIL SIDES OF PANELS AND BOTTOMS TO SHEAR TOP PLATE 7) NAIL SHED ROOF FRONT LEDGER MARKED IN BLACK 8) INSTALL PLYWOOD AT ENTRY, CLOSURE WALL 9) NAIL TRUSS BOTTOM CHORD TO WALL AT 93/SD-3 10) LATERAL TRUSS BRACES AT HVAC 12) NAIL SHEAR ABOVE SNUB NOSE TRUSSES, SHEAR ABOVE CEILING TO BOTTOM CHORD |