Permit: T02CM05419

Parcel: 110034270

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Permit Number - T02CM05419

Inspection Description - BUILDING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
05/23/2003 BUILDING - FINAL Approved IVRS - Inspection 0000*
05/21/2003 BUILDING - FINAL Denied IVRS - Inspection 0999*/ 1) CORRECTIONS NOT DONE
05/20/2003 BUILDING - FINAL Denied IVRS - Inspection 0999*/ 1) CIRCUIT #20 BREAKER WON'T RESET 2) INSTALL BLANK AT OPENING IN PANEL FRONT AND BOTTOM 3) KITCHEN GFCI OUTLETS DON'T TRIP/STAY HOT WHEN TRIPPED FROM DOWN STREAM-(LINE/CODE REVERSE) 4) CUT CLEANOUT TO GRADE 5) ENGINEER LETTER REQUIRED FROM 3/12 INSPECTION 6) PROVIDE LADDER TO ATTIC