Inspection Status: Approved
Inspection History: PLUMBING - ROUGH, SOIL
Permit Number - T02CM05410
Inspection Description - PLUMBING - ROUGH, SOIL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/08/2003 | PLUMBING - ROUGH, SOIL | Approved | IVRS - Inspection 0000* | |
05/07/2003 | PLUMBING - ROUGH, SOIL | Not ready for Inspection | IVRS - Inspection 0000* | |
05/06/2003 | PLUMBING - ROUGH, SOIL | Denied | IVRS - Inspection 0999* 1.) WET VENTING IS LIMITED TO VERTICAL DRAINAGE PIPING MAY NOT HAVE HORIZONTAL DRAINAGE PIPING ON WET VENTED SECTION. 2.) HORIZONTAL X HORZONTAL CHANGE OF DIRECTION TO BE THRU WYE BRANCH OR EQUIVILENT SWEEP. 3.) FIX LEAKS ON ABS. 4.) PLAN SHOW 2-3" VENTS HOWEVER. 5.) IF TOTAL DFU EXCEED 36 DFU YOU WILL BE REQUIRED TO PROVIDE 12.56 AREA OF VENTING. |