Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T02CM05370
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/28/2005 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 02/02/2005 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1) CONDENSATE OVERFLOW ON A/H PLUG AUX. OVERFLOW PORT. 2) COMPLETE DATA PLATE. AUXILIARY HEAT STRIPS, YES? NO? WHAT SIZE. 3) CONTROL WIRING SPLICE, PROVIDE J BOX 4) HI VOLTAGE CARFLEX 3/4" PROVIDE CLEAR ACCESS ON FRONT OF PANEL. 5) CHECK FOR FILTERS REMOVAL. |