Permit: T02CM05370

Parcel: 106030720

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T02CM05370

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
04/08/2005 ELECTRIC - FINAL Approved IVRS - Inspection :*APPROVED
03/28/2005 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999* 1) 3 COMPRESSOR DISCONNECT ON WEST SIDE REQUIRE CLEARANCE IN FRONT OF AS PER 2002 NEC 110-26. 2) SAME ON EAST SIDE, AS # 1 ABOVE.
02/02/2005 ELECTRIC - FINAL Partial Approval IVRS - Inspection :* SUBJECT TO BOND OK TO CLEAR IS BOND NEEDED? SIX RES. APT. UNITS. CALL TOM 400-5194. OK TO CLEAR ALL UNITS FOR POWER. CALLED TOM FROM LINEAR CONST TO ADVISE A BOND FOR TEMP POWER IS REQUIRED PRIOR TO RELEASE OF POWER.