Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/04/2004 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 09/28/2004 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) PANEL CABLE ENTRYS MUST BE CLAMPED-2 GRAY CABLES JUST GOING THRU PLASTIC INSERTS 2) PASS THRU PENETRATIONS IN PVC SEALED WITH ? M CAULKING SHOULD BE STEEL NOT PLASTIC 3) INSTALL FLEX ON #10 CABLES IN FURNACE ROOM SO FLEX CAN BE STAPLED AND SUPPORTED INSIDE WALL NOT JUST PUSHED IN 4) FIRE CAULKING MISSED ON SOEM CONDUITS, 1ST FLOOR NORTH MID SECTION 5) 2ND FLOOR EAST APT 3 GANG SW RUN ROMEX INTO BOX ALL THE WAY, FLEX ON ROMEX COMING OUT OF WALL TO BE NAILED TO WALL |