Permit: T02CM05367

Parcel: 11302139D


Addresses:

1239 E PRINCE RD

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
04/16/2003 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
03/26/2003 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection 0000*
12/19/2002 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*1.) FINISH #6 PREVIOUS INSPECTION.
OK TEMP C OF O SUBJECT TO OTHER INSPECTIONS AND POSTING OF BOND.
12/17/2002 ELECTRIC - FINAL Denied IVRS - Inspection 0999*
1.) SUPPORT FLEX CONDUIT TO POWER POLES AS PER CODE
2.) BOND POWER POLE JUNCTION BOXES.
3.) APPROVED EXTENDER RINGS ARE NEEDED WHERE MORE THAN 1/4" BETWEEN DEVICE AND BOX
4.) FINISH SUPPORTING DATA CORRECTLY.
5.) MAINTAIN WORKING CLEARENCE AT SERVICES
6.) PLANS CALL FOR VERIFICATION OF SERVICE FEEDERS TO 260AMP. WE HAVE 3/0 COPPER IN CONDUIT (RHH/RHN) UNDERGROUND.