| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/16/2003 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* | |
| 03/26/2003 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection 0000* | |
| 12/19/2002 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*1.) FINISH #6 PREVIOUS INSPECTION. OK TEMP C OF O SUBJECT TO OTHER INSPECTIONS AND POSTING OF BOND. |
|
| 12/17/2002 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999* 1.) SUPPORT FLEX CONDUIT TO POWER POLES AS PER CODE 2.) BOND POWER POLE JUNCTION BOXES. 3.) APPROVED EXTENDER RINGS ARE NEEDED WHERE MORE THAN 1/4" BETWEEN DEVICE AND BOX 4.) FINISH SUPPORTING DATA CORRECTLY. 5.) MAINTAIN WORKING CLEARENCE AT SERVICES 6.) PLANS CALL FOR VERIFICATION OF SERVICE FEEDERS TO 260AMP. WE HAVE 3/0 COPPER IN CONDUIT (RHH/RHN) UNDERGROUND. |