Inspection Status: Approved
Inspection History: PLUMBING - ROUGH, SOIL
| Date |
Description |
Inspector |
Results |
Comments |
| 01/21/2003 |
PLUMBING - ROUGH, SOIL |
|
Approved |
IVRS - Inspection 0000* |
| 01/17/2003 |
PLUMBING - ROUGH, SOIL |
|
Denied |
IVRS - Inspection 0999*/ 1) CHICAGO LOOP NOT GLUED 2) PROVIDE NEW WATER TEST FOR ENTIRE SYSTEM 3) BRIDGING NOT ALLOWED-ENTIRE RUN TO HCS CONNECTION MUST BE SITTING ON A FIRM BED OF DIRT. DO NOT BACKFILL AROUND HCS CONNECTION AREA |
| 01/16/2003 |
PLUMBING - ROUGH, SOIL |
|
Denied |
IVRS - Inspection 0999*/ 1) AT 1ST BRANCH 3 X 3 X WYE. 2" PIPING NOT GLUED TO WYE (LEAKING) 2) REPAIR AND FILL SYSTEM TO 10' HEAD 3) TEST CAP AT SOUTH 4" CLEAN OUT HAS SMALL LEAK 4) OK TO BACKFILL AROUND HCS ONLY |