Inspection Status: Approved
Inspection History: PLUMBING - ROUGH, SOIL
| Date |
Description |
Inspector |
Results |
Comments |
| 10/15/2003 |
PLUMBING - ROUGH, SOIL |
|
Approved |
IVRS - Inspection 0000*/ 1) GAS PIPING DOES NOT CHANGE SIZE MID BRANCH. 2) HAVE PLUMBING YARDWATER (03040) AND SEWER/HCS (03055) ADDED TO PERMIT. 3) REVIEWED CORRECTIONS REQUIRED AT GREASE TRAP WITH PLUMBER. 4) SILFOSED REPAIR UNDERSLAB OK TO COVER. 5) ABS DWV THROUGH ROOF OK. 6) COPPER OK. 7) CLOSET FLANGES OK. |
| 10/07/2003 |
PLUMBING - ROUGH, SOIL |
|
Denied |
IVRS - Inspection 0999* |
| 10/06/2003 |
PLUMBING - ROUGH, SOIL |
|
Denied |
IVRS - Inspection 0999* |
| 09/22/2003 |
PLUMBING - ROUGH, SOIL |
|
Denied |
IVRS - Inspection 0999*/ LEAD SOLDERED JOINTS BELOW SLAB NOT PERMITTED. MUST BE SIL FAS'D OR SILVER BRAZED. |
| 09/18/2003 |
PLUMBING - ROUGH, SOIL |
|
Not ready for Inspection |
IVRS - Inspection 0000*/ COPPER NOT REPAIRED. |
| 09/16/2003 |
PLUMBING - ROUGH, SOIL |
|
Partial Approval |
IVRS - Inspection 0000*/1) PLUMBING UNDER SLAB EXPOSED FOR INSPECTION. REPLACE DAMAGED SECTION OF COPPER. - OK TO COVER THE REST. 2)OK TO INSTALL CLEAN-OUT AD PT WITH FRANK PATTERN C.O. COVER IN BATHROOMS. |
| 09/15/2003 |
PLUMBING - ROUGH, SOIL |
|
Not ready for Inspection |
IVRS - Inspection 0000* |
| 09/12/2003 |
PLUMBING - ROUGH, SOIL |
|
Denied |
IVRS - Inspection 0999*/ 1) NO APPROVED PLAN ON SITE |
| 09/11/2003 |
PLUMBING - ROUGH, SOIL |
|
Not ready for Inspection |
IVRS - Inspection 0000*/ 1) NOT READY FOR INSPECTION |
| 08/12/2003 |
PLUMBING - ROUGH, SOIL |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) ABS DWV UNDERGROUND IN STORAGE AND BATHROOM AREAS, OK. 2) WASTE FROM GREASE TRAP THROUGH BLDG - OK. WATER TEST ONE RISER TO TEN FEET OK. |
| 08/11/2003 |
PLUMBING - ROUGH, SOIL |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) ALL PIPING INSIDE COVERED WITHOUT INSPECTION. 2) FIGURE FIVE MAY NOT BE INSTALLED IN A HORIZONTAL POSITION - CAN SEAL BACK PITCH ON WATER CLOSETS. 3) REMOVE 2 WAY CLEAN-OUT IN BATH ROOM. |
| 07/17/2003 |
PLUMBING - ROUGH, SOIL |
|
Denied |
IVRS - Inspection 0999*/ 1) NOT INSTALLED PER PLAN. HAVE PLUMBER ON SITE AT TIME OF NEXT INSPECTION. PLEASE HAVE A COPY OF COMMERCIAL PLUMBING LICENSE. 2) CONTRACTOR TO PAY REINSPECTION FEE. |
| 07/14/2003 |
PLUMBING - ROUGH, SOIL |
|
Denied |
IVRS - Inspection 0999*/ 1) PLEASE POST YOUR ADDFRESS SO THAT IT CAN BE SEEN FROM WEST CONGRESS ST. 2) NO CHANGE FROM LAST INSPECTION 3) YOU MUST INSTALL PER APPROVED PLAN |
| 07/09/2003 |
PLUMBING - ROUGH, SOIL |
|
Denied |
IVRS - Inspection 0999*/NOT INSTALLED PER PLAN. |