Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T02CM05337
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/14/2003 | PLUMBING - INTERMEDIATE | Approved | ||
02/27/2003 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection 0000*PLEASE PROVIDE AN APPROVED REVISED PLAN FOR ALL GAS LINES WITH TOTAL LENGTH & TOTAL BTU'S. ALSO NOT INSTALLED AS PER REVISED PLAN ON JOB PLAN CALLS FOR 1 1/2 1" HAS BEEN INSTALLED. WATER NO REVISED PLAN ON JOB FOR WATER PLEASE PROVIDE APPROVED REVISED PLAN. TEST ON ROOF DRAIN OK. |
|
02/26/2003 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection 0000*1.) GAS LINE ABOVE CEILING NOT INSTALLED AS PER APPROVED PLAN PLEASE PROVIDE APPROVED REVISED DRAWING WITH TOTAL LENGTH & TOTAL BTU'S FORM POINT OF CONNECTION TO FIXTURES SHOW ALL BRANCHES. 2.) NO REVISED PLAN ON AS PER LAST REQUEST PLEASE PROVIDE AS BUILD DRAWING VENTS & WATER ECT. 3.) ROOF DRAIN COVERED WITHOUT TEST NO OVER FLOW DRAIN ON PLAN. 4.) ALL WALLS COVERED AT THIS TIME INSULATION. |
|
02/20/2003 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*TEST ONLY WASTE VENTS WATER OK SUBJECT TO APPROVED REVISED AS BUILD DRAWING. NO TEST ON ROOF DRAIN NOT ON PLUMBING DRAWINGS OR ON ROOF PLAN? PLEASE COMPLETE INSULATION ON HOT WATER LINES AS PER SPEC. NO INFO ON GAS LINE AT THIS TIME. PLEASE PROVIDE FINISH FLOOR ELV RIM ELU. OF UP STREEM MAN HOLE FOR OUR RECORDS. |
|
02/19/2003 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection 0999*GAS LINE INSTALLED WITH OUT INSP'S IN TI TO DENTAL OFFICE CODE VIOLATION SEC 1206.0 UNABLE TO LOCATE METER SET. NO INSPECTION HAVE BEEN MADE & NO PRESSURE TEST AT THIS TIME WILL CALL STEVE FOR UPDATE. PLEASE PROVIDE PROPER PERMITS PROVIDE APPROVED DRAWING W/TOTAL LENGTH & TOTAL BTU'S PROVIDE PRESSURE TEST AS REQUIRED BY CODE & CALL FOR INSP. |
|
02/18/2003 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection 0000*WILL REQUIRE TEST ON VENTS THROU ROOF TEST ON WATER. NEED REVISED PLAN FOR WATER UNDER SLAB NO PRESSURE TEST ON NEW GAS LINE OVER HEAD? |
|
01/27/2003 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection 0000* |