Permit: T02CM05337

Parcel: 12710017D


Addresses:

899 N WILMOT RD #C1


Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Permit Number - T02CM05337

Inspection Description - PLUMBING - ROUGH, SOIL

Inspection Status - Approved

Date Description Inspector Results Comments
01/30/2003 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection 0000*ALSO 1/2 WATER LINES HAVE BEEN INSTALLED TO DENTAL CHAIRS SUBJECT TO APPROVED REVISED PLANS AS PER OUR OFFICE NOTE PERMITS OUR REQUIRED FOR BACK FLOW DEVICES.
PLEASE NOTE INSP IS REQUIRED ON VACCUM LINES FOR DENTAL CHAIRS THIS INSP BE MADE BY MECH. INSP.
01/17/2003 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection 0000*1.) TEST OK ON UNDERGROUND SOIL ONLY PLEASE CALL FOR ROUGH SOIL (SO I CAN SEE THE PRE SLAB WITH WRAP AROUND ABS.
2.) AFTER LOOKING OVER YOUR PLAN THE 94 UPC REQUIRES AN APPROVE RECEPTOR FOR INDIRECT WASTE. NOT A P-TRAP SEC VACUUM DRAIN. DRAIN PLEASE TALK WITH YOUR ARCHITECT. PROVIDE INFO AT TIME OF NEXT INSP.
3.) ALSO CODE VIOLATION ON DEVELOPE DRAIN SEE SEC 1001.0 ONLY 1TRAP PERMITTED ON A TRAP ARM. I BELIEVE THIS PLAN HAS BEEN APPROVED IN ERROR PLEASE MAKE CORRECTIONS BY NEXT INSP WITH PROPER REVISIONS.