Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/26/2003 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* | |
| 03/21/2003 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection 0000*1.) APPROVED EXTENDER RINGS NEEDED 2.) "B" PHASE AT PANEL LUG IS LOOSE TO BUSS. 3.) FINISH INSTALLATION OF DEVICES AND WATER HEATER. W/H TO HAVE A DISCONNECTING MEANS. 4.) JUNCTION BOX TO BE 6 X DIAMETER OF CONDUIT 5.) SUPPORT CONDUIT FROM BOX WITHIN 3' |