Permit: T02CM05324

Parcel: 12107462C


Addresses:

5920 E PIMA ST #100


Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T02CM05324

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
03/28/2003 MECHANICAL - FINAL Approved
03/27/2003 MECHANICAL - FINAL Partial Approval IVRS - Inspection 0000* 1) LAJBEL AIR HANDLERS 2) PROVIDE FUSES IN ELEC. DISCONNECTS 3) COVER OPENINGS WHERE HEAT STRIPS WOULD BE INSTALLED. MARK DATA PLATES AS SUCH. 4) NEED TO SEE SECONDARY DRAINS INSTALLED CORRECTLY. PROVIDE TRAPS. 5) EQUIPMENTS ON ROOF NOT READY. RECALL FOR INSPECTION.