Permit: T02CM05324

Parcel: 12107462C


Addresses:

5920 E PIMA ST #100


Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Permit Number - T02CM05324

Inspection Description - MECHANICAL - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
03/21/2003 MECHANICAL - INTERMEDIATE Approved IVRS - Inspection 0000*
03/20/2003 MECHANICAL - INTERMEDIATE Denied IVRS - Inspection 0999*
1.) SECONDARY DRAIN MUST BE PIPED TO A CONSPICUOUS LOCATION.
2.) PROVIDE DUCT SMOKE DETECTOR AS PER PLANS.
3.) PROVIDE OUTSIDE AIR INTAKES AS PER PLANS
4.) AIR HANDLERS ARE NOT ACCESSIBLE FOR SERVICE OR REPAIR. THEY WILL HAVE TO BE COMPLETELY REMOVED TO REPAIR. PLEASE PROVIDE PETITION OF APPEAL FROM THE CODE ADMINISTRATOR.