Inspection History: PLUMBING - ROUGH, SOIL

Date Description Inspector Results Comments
01/29/2003 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection 0000*/ 1) SOIL WATER TEST IS OK 2) P.O.C. OF NEW BLDG DRAIN TO EXISTING BLDG DRAIN IS OK 3) OK TO BACKFILL TRENCH 4) OVERHEAD DISTRIBUTION IS OK 5) OK TO DRYWALL
01/27/2003 PLUMBING - ROUGH, SOIL Denied 1.) OUTLET OF VENT CAN NOT BE BELOW THE TRAP. THIS VENT MUST BE ABOVE THE CENTER LINE OF OUTLET DRAIN.
2.) DO NOT COVER.
01/23/2003 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection 0999*
1.) GREASE TRAP MUST BE VENTED PROPERLY
2.) WILL REQUIRE A REVISED & APPROVED
DRAWING ON WASTE & VENT SYSTEM FOR GREASE TRAP.
3.) 3" TRAP ARM FOR FLOOR SINK DOSE NOT MEET MIN TRAP ARM DISTRANCE.