Inspection History: PLUMBING - ROUGH, SOIL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/29/2003 | PLUMBING - ROUGH, SOIL | Approved | IVRS - Inspection 0000*/ 1) SOIL WATER TEST IS OK 2) P.O.C. OF NEW BLDG DRAIN TO EXISTING BLDG DRAIN IS OK 3) OK TO BACKFILL TRENCH 4) OVERHEAD DISTRIBUTION IS OK 5) OK TO DRYWALL | |
| 01/27/2003 | PLUMBING - ROUGH, SOIL | Denied | 1.) OUTLET OF VENT CAN NOT BE BELOW THE TRAP. THIS VENT MUST BE ABOVE THE CENTER LINE OF OUTLET DRAIN. 2.) DO NOT COVER. |
|
| 01/23/2003 | PLUMBING - ROUGH, SOIL | Denied | IVRS - Inspection 0999* 1.) GREASE TRAP MUST BE VENTED PROPERLY 2.) WILL REQUIRE A REVISED & APPROVED DRAWING ON WASTE & VENT SYSTEM FOR GREASE TRAP. 3.) 3" TRAP ARM FOR FLOOR SINK DOSE NOT MEET MIN TRAP ARM DISTRANCE. |