Permit: T02CM05318

Parcel: 11628001E

Inspection Status: Approved

Inspection History: ELECTRIC - UNDERGROUND

Date Description Inspector Results Comments
12/29/2004 ELECTRIC - UNDERGROUND Approved IVRS - Inspection :*
05/04/2004 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :
See detailed listing on site.| 999*/ 1) SERVICE SES-2 (BLDG G & H) 2) TEP TO SW GEAR, 10 4" PVC'S OK TO COVER 3) SWITCH GEAR SES 2-ALL UNDERGROUND FEEDERS ENTERING OK TO COVER 4) TRANSFER SW'S UNDERGROUND OK TO COVER 5) EXTENDED 3/0 UFER OK TO COVER 5) EM DISTRIBUTION J-BOX CONDUITS OK TO COVER 6) ALL ABOVE OK TO COVER
10/30/2003 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection 0000*/ NOTES: OK UNDERGROUND AND STUB UPS FOR SWITCH GEAR AT SEC. '3' AND SES '4' , OK UFER GROUNDING SYSTEM.
10/21/2003 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection 0000*/ NOTES: OK UNDERGROUND, STUB UPS AND UFER. GROUNDING FOR ELECTRIC ROOM P-2 OF 'G' BLD.
10/06/2003 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection 0000*/ OK CONTINUE DUCT BANK 'C' 'D' RISER AND PHONE TO STAIRWELL NORTH EAST BLDG 'E'
10/03/2003 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection 0000*/1) AREA '6' FLOOR AREA UNDERGROUND OK. 2) EXTENSION OF BANK DUCT OUT OF AREA 'D'
09/25/2003 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection 0000*/ 1) OK FEEDER CONDUIT AND BRANCH CIRCUIT FOR POWER AND LIGHTING AT P2 ELECTRIC ROOM AND AREA 2
09/16/2003 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection 0000*/1) OK PIGA AND PIGB PANEL FEEDERS. OK STUB UPS. 2) OK EAST PARKING GARAGE LTG AND RECEPT. BRANCH, PI LEVEL.
09/15/2003 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection 0000*/1) OK U.G. FEEDERS AND STUB UPS FOR ELECTRIC RM 'DE'. 2) OK TELEPHONE DUCTS AREA 'B' AND 1-1/2" CONDUIT FOR PNL 'PIBC'. 3) OK GROUND RODS - UFER.
09/08/2003 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection 0000*/ OK NORTH AREA 'I' PARKING GARAGE, LIGHTING CIRCUITS.
09/03/2003 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection 0000*/ NOTES: 1) OK 4" STUB-UPS FOR PHONE INTO 201 PHONE ROOM AND STUBS FOR 2ND FLOOR
08/28/2003 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection 0000*/ OK PANEL FEEDERS CPH-1, CPH-2, OK LIGHTING, CIRCUITS, PARKING AREA P-1, SOUTH AREA 'J'.
08/26/2003 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection 0000*/1) EMERGENCY CONDUITS J-BOX TO JJ 2-2", 5-2-1/2", 1-3", 1-1" PVC. OK TO COVER. 2) 2-4" PVC'S PNL IP2HA AND IP2PB FEEDER FROM MECH ROOM QQ LINE. BOTH RUNS OK TO COVER
08/21/2003 ELECTRIC - UNDERGROUND Not ready for Inspection IVRS - Inspection 0000*
08/20/2003 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection 0000*/ 1) OK-3-4" PANEL FEEDER FROM SOUTH WEST GEAR TO BLDG I-J PARKING GARAGE, ALSO 1-2 1/2, 1-2", 1-1", 2-4" SPARE
08/19/2003 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection 0000*/ 1) OK PHONE DUCTS FROM MAIN PHONE ROOM TO BRIDGE AND TO ABC RISER. 2) OK BRANCH CKT CONDUIT IN SLAB FOR LIGHTING PARKING GARAGE P-3 LEVEL.
08/16/2003 ELECTRIC - UNDERGROUND Partial Approval 1) 4-4" TELEPHONE DUCTS STUB-UP AND THRU RETAINING WALL 'D' WEST 2) SAT AFTER HOURS INSPECTION REQUEST PER WEITZ CONST. PAID $102.00 #435
08/14/2003 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection 0000*/OK GENERATOR FEEDER FROM GENERATOR ROOM TO COLUMN 'QQ'.
08/04/2003 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection 0000*/ 1) OK DATA AND FEEDERS FOR ABC AND DE RISERS CONTINUED FROM AREA 'D' AND AREA 'E'
07/25/2003 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection 0000*/OK TO COVER. 8-4" PVC'S DUCT BANK FEEDERS./ 2-3" PVC'S EM GENERATOR FEED./ 1-1-1/2 PVC LITE SAFETY./ 1-1" PVC CONTROL/ D-WEST TO D-EAST ( NORTH SIDE OF RETAINING WALL P-1 LEVEL.)
07/14/2003 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection 0000*/OK UFER BOND 3/0 COPPER TO REBAR FOR ELECT. EQUIP. BONDING IN ELECTRIC ROOM ABC.
07/01/2003 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection 0000*/ 1) AREA ABC ELECTRIC ROOM TO COLUMN LINE '0' POOL KITCHEN AREA, AS FOLLOWS: 6-1" AREA LTG. 1-2" FEED TO PANEL B-2 PHA 1-2 1/2" TO POOL EQUIPMENT 3) UNDERGROUND OK, AS INSTALLED, STILL NO APPROVED PLAN