Permit: T02CM05318

Parcel: 11628001E

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Date Description Inspector Results Comments
12/29/2004 BUILDING - FINAL Approved IVRS - Inspection :*
1) NO C OF O WAIT FOR T03CM02796
06/05/2003 BUILDING - FINAL Not ready for Inspection IVRS - Inspection 0000*/ 1) MEETING WITH MARK GUIDONE AND FRED PECH OF WEITZ ADN PHIL HAYWARD AT SCHNIEDER AND ASSOCIATES ABOUT SW12 2) CONFIRMED THAT CITY OF TUCSON (MYSELF) AND PHIL VERIFIED THAT ALL SPLICES WERE DONE PER STEVE SLOANAKERS DESIGN (RFI 68). LAP LENGHTS WERE 12'-3"/12'-6". ALL POSITIONING WAS WITHIN 1" OF DESIGN. MINIMUM CLEARANCE BETWEEN ADJACENT WAS 2" WHERE SPLICE WAS NOT EXACTLY PER DESIGN (SLIGHT OFF SET FOR FIELD INSTALL PURPOSE) 3) 4KLB CONCRETE MADE WITH 1/2" AGGREGATE WAS PLACED AND MECHANICALLY CONSOLIDATED IN 2' LIFTS. MINIMUM CLEARANCE FROM #114 BARS TO FACE IS 2" 2) THE QUESTION IS NOT WHETHER OR NOT WALL WAS BUILT PER PLAN (RFI68) BUT WHETHER ENGINEERING DESIGN IS SUFFICIENT
06/02/2003 BUILDING - FINAL Not ready for Inspection IVRS - Inspection 0000*/ 1) DO NOT BACKFILL AROUND SW12, UNTIL FURTHER NOTICE. PER BLDG OFFICIAL DAVID MANN. RE: #14 SPLICES
05/21/2003 BUILDING - FINAL Partial Approval