Permit: T02CM05317

Parcel: 126130200


Addresses:

4590 E BROADWAY BL


Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T02CM05317

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
11/22/2004 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
11/19/2004 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) COMPLETE ALL, NEED GROUNDING BUSHINGS AND BOND JUMPER FOR SERVICE EQUIPMENT THRU-OUT
2) PHASING SEQUENCE ON COLOR CODE IS IMPROPER, PLEASE HABE BLK-RED AND BLUE, LEFT TO RIGHT
3) PLAN HAS COPPER, NO ALUMINIMUM BUILD SERVICE PER PLAN
05/17/2004 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*/ FRONT SOFFITS AND COLUMN.