Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/22/2004 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 11/19/2004 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) COMPLETE ALL, NEED GROUNDING BUSHINGS AND BOND JUMPER FOR SERVICE EQUIPMENT THRU-OUT 2) PHASING SEQUENCE ON COLOR CODE IS IMPROPER, PLEASE HABE BLK-RED AND BLUE, LEFT TO RIGHT 3) PLAN HAS COPPER, NO ALUMINIMUM BUILD SERVICE PER PLAN |
|
| 05/17/2004 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :*/ FRONT SOFFITS AND COLUMN. |