Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T02CM05315

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
02/28/2003 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection 0000*
02/25/2003 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0999*
ALL WIRES IN BOXES MUST BE MADE UP.
THE USE OF SINGLE CONDUCTORS TO BUNDLE CABLER TOGETHER IS NOT CORRECT. USE TY-RAPS OR OTHER BRAND OF CABLE TIE.
FINISH WIRING AT FIREPLACE AREA.
02/13/2003 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*FURN. PER PLAN WILL REQUIRE A 40 AMP BREAKER.
RANGE HAS 50 AMP BREAKER TO AND #8-3 ROMEX IS RATED FOR 40 AMP NEC 336-26.
STORAGE ROOM RECEPT, MUST BE UP 18" FROM GARAGE FLOOR LEVEL. AT LOWER AREA.
A BOX IS REQUIRED FOR THE WALL BATH FIXTURE (UNLESS LISTING IS OBTAINED.)
ADD WIRE PROTECTION PLATE AT AREAS IE. ABOVE BATHROOM.
OK TO INSULATE.
SUBJECT TO OTHER INSPECTION.
FURTURE UNDERGROUND CONDUCT TO PATIO APPROVED.